Voltage drop calculator with wire size

Enter the voltage, conductor, size, length and load. See the voltage drop in volts and percent, what is left at the load, and the smallest wire that both carries the current and keeps the drop under 3% or 5%.

3% / 5%NEC informational guideline
14 AWG to 750Copper and aluminum
FreeNo email, no sign-up
System
Conductor
ft
From the panel to the load. The math counts the return path.
A
For a continuous load (3 hours or more), the NEC sizes the wire at 125% of it.
Drop to stay under
Voltage drop
2.49%
5.97 V lost, 234 V at the load
10 AWG copperSuggested wire
121 ftMax length at 3%
30 AThis wire carries
The NEC's 3% and 5% figures are informational notes, not requirements. The NEC as adopted locally and the inspector decide what is allowed.

How we got this

  1. FormulaVD = 2 × K × I × L ÷ CMK is the resistance of a 1 circular mil, 1 ft wire at 75°C: 12.9 ohms for copper, 21.2 for aluminum. The 2 counts the wire out and the wire back.
  2. Voltage drop2 × 12.9 × 24 A × 100 ft ÷ 10,380 cmil (10 AWG) = 5.97 V
  3. Percent5.97 ÷ 240 V = 2.49%, leaving 234 V at the load
  4. Ampacity10 AWG copper carries 35 A at 75°C (NEC Table 310.16); the breaker is capped at 30 A by NEC 240.4(D)Assumes 75°C terminations and no more than three current-carrying conductors in the raceway. Bundling, hot attics and rooftops derate it.
  5. Smallest wire that works10 AWG copper (10 AWG for the current, 10 AWG for a 3% drop)
SizeMax ampsDropPercentFor this run
14 AWG15 A15.07 V6.28%Too small for the current
12 AWG20 A9.48 V3.95%Too small for the current
10 AWG30 A5.97 V2.49%Works
8 AWG50 A3.75 V1.56%Works
6 AWG65 A2.36 V0.98%Works
4 AWG85 A1.48 V0.62%Works
3 AWG100 A1.18 V0.49%Works
2 AWG115 A0.93 V0.39%Works
1 AWG130 A0.74 V0.31%Works
1/0150 A0.59 V0.24%Works
2/0175 A0.47 V0.19%Works
3/0200 A0.37 V0.15%Works
4/0230 A0.29 V0.12%Works
250 kcmil255 A0.25 V0.1%Works
300 kcmil285 A0.21 V0.09%Works
350 kcmil310 A0.18 V0.07%Works
500 kcmil380 A0.12 V0.05%Works
600 kcmil420 A0.1 V0.04%Works
750 kcmil475 A0.08 V0.03%Works

Sources: ExpertCE, Acceptable voltage drop per the NEC (210.19 and 215.2 informational notes, K values); Cerrowire ampacity chart (NEC Table 310.16, 75°C column); NFPA 70, National Electrical Code (Chapter 9, Table 8; 240.4(D)). Checked 2026-10-08.

Key takeaways
  • Voltage drop = 2 × K × amps × one-way length ÷ circular mils for single phase, with K = 12.9 for copper and 21.2 for aluminum. Three phase uses 1.732 instead of 2.
  • The NEC suggests keeping branch circuits under 3% and feeder plus branch under 5%. It is an informational note, not a requirement.
  • A wire big enough for the current can still be too small for the distance. Check both, and use the bigger size.

The voltage drop formula

Every wire has resistance, so some voltage is lost pushing current along it. The longer the run, the more current, and the thinner the wire, the more is lost.

Single phase: VD = 2 × K × I × L ÷ CM

Three phase: VD = 1.732 × K × I × L ÷ CM

  • K is the resistance of a wire one circular mil in area and one foot long at 75°C: about 12.9 ohms for copper and 21.2 for aluminum.
  • I is the load current in amps.
  • L is the one-way length in feet, from the panel to the load.
  • CM is the conductor's area in circular mils, from NEC Chapter 9, Table 8.

The 2 counts the wire out and the wire back. In a balanced three phase circuit the return is shared, so the multiplier is √3, or 1.732. Percent drop is VD divided by the system voltage.

SizeCircular milsCopper ampacity, 75°CAluminum ampacity, 75°C
14 AWG4,11020 (15 A breaker max)n/a
12 AWG6,53025 (20 A breaker max)20 (15 A breaker max)
10 AWG10,38035 (30 A breaker max)30 (25 A breaker max)
8 AWG16,5105040
6 AWG26,2406550
4 AWG41,7408565
2 AWG66,36011590
1/0105,600150120
2/0133,100175135
4/0211,600230180
250 kcmil250,000255205
500 kcmil500,000380310

Ampacities are the 75°C column of NEC Table 310.16. The breaker limits on 14, 12 and 10 AWG come from the small-conductor rule in NEC 240.4(D).

Worked examples

A 120 V circuit in a detached garage. 16 A of load, 100 ft away, 12 AWG copper:

VD = 2 × 12.9 × 16 × 100 ÷ 6,530 = 6.32 V. That is 6.32 ÷ 120 = 5.27%, leaving 113.7 V at the load. 12 AWG carries the current, but the drop is well over 3%. 10 AWG gives 3.31%, still over. 8 AWG gives 2.08%, which works.

A 240 V EV charger. A 48 A charger, 150 ft from the panel. The NEC treats EV charging as a continuous load, so the circuit is 60 A and the wire has to carry it. 6 AWG copper (65 A at 75°C) gives 2 × 12.9 × 48 × 150 ÷ 26,240 = 7.08 V, 2.95%. That just makes 3%. 8 AWG would give 4.69%, and it is too small for a 60 A circuit anyway.

A 480 V three phase feeder. 100 A on 200 ft of 1/0 aluminum: 1.732 × 21.2 × 100 × 200 ÷ 105,600 = 6.95 V, 1.45%.

CircuitWireLongest run at 3%
120 V, 15 A14 AWG copper38 ft
120 V, 20 A12 AWG copper46 ft
240 V, 24 A10 AWG copper121 ft
240 V, 30 A10 AWG copper97 ft
240 V, 40 A8 AWG copper115 ft
240 V, 50 A6 AWG copper146 ft
240 V, 100 A2/0 copper371 ft

These assume the circuit is loaded to its full rating. Real loads are often lower, so real drops are often smaller. The calculator works from the current you enter.

What the NEC says about voltage drop

The NEC's voltage drop guidance sits in informational notes after 210.19 (branch circuits) and 215.2 (feeders). They say that conductors sized to keep voltage drop under 3% on a branch circuit, and under 5% for the feeder and branch together, give reasonable efficiency of operation.

Informational notes explain; they are not requirements. An inspector cannot fail a job on the 3% figure unless the local jurisdiction has adopted it, though some energy codes and specifications do make voltage drop limits mandatory. A few NEC sections do set real limits for specific equipment, such as fire pumps and sensitive electronic equipment.

So why bother? Low voltage makes motors draw more current and run hot, shortens their life, dims lights, and can trip electronics and make compressors struggle to start. On long runs, it also wastes power as heat in the wire, every hour the load runs.

The NEC and the inspector governThis calculator sizes for voltage drop and the 75°C ampacity table. The NEC as adopted where you work, the equipment's listing and instructions, and the local inspector decide what is allowed.

Picking the wire size

Size every conductor for two things, then use the bigger of the two:

  1. Ampacity. The wire has to carry the current. The calculator uses the 75°C column of Table 310.16, the usual rating for terminations on 100 A and larger equipment and on most breakers listed for 75°C, plus the 240.4(D) caps on 14, 12 and 10 AWG. If your terminations are only rated 60°C, use the 60°C column instead, which is lower for small wire.
  2. Voltage drop. The wire has to be big enough that the drop stays under your target over the run.

The calculator finds both and suggests the larger. It also shows the longest run your chosen wire can go at the drop limit, which is handy for quoting a detached garage, a well pump or a landscape lighting run.

Ampacity can be reduced further for things this calculator does not check: more than three current-carrying conductors in a raceway, high ambient temperatures such as a hot attic or a rooftop in the sun, and the 125% rule for continuous loads (three hours or more), which applies to EV chargers, water heaters and many HVAC loads. Apply those corrections and adjustments before you settle on the size.

Voltage drop on common jobs

Some runs come up again and again, and they are where voltage drop catches people out:

  • Detached garages and shops. A 120 V circuit to a garage 75 ft away is already past the 3% figure at 20 A on 12 AWG. Run a 240 V feeder to a subpanel instead, or upsize the branch circuit.
  • Well pumps. Long runs to a submersible pump drop voltage at the moment the motor starts, when current is highest. Pump makers publish maximum cable lengths by wire size and motor size; follow those, since they account for starting.
  • Outdoor and landscape lighting. Low-voltage lighting runs at 12 V, so a drop of a single volt is over 8%. Use the transformer maker's guidance, or center-feed long runs.
  • EV chargers. A 48 A charger is a 60 A circuit and a long run from the panel to a driveway is common. The 150 ft example above needed 6 AWG copper to stay at 3%.
  • HVAC condensers. Compressors are sensitive to low voltage at start. The nameplate gives the minimum circuit ampacity to size the wire; check the drop on long runs to rooftop or remote units.

In each case the fix is the same: a bigger conductor, a higher voltage, or a shorter run. Raising the voltage is the most powerful: the same load at 240 V draws half the current of 120 V, and the same volts lost are half the percentage.

Reading the results table

Under the answer, the calculator lists every size of the conductor you picked, from the smallest to 750 kcmil, with the maximum current each can be protected at, the drop in volts, the percent, and a verdict for your run:

  • Works: carries the current and stays under the drop you chose.
  • Too small for the current: the ampacity, or the 240.4(D) breaker cap for 14, 12 and 10 AWG, is below your load.
  • Over 3% (or 5%): carries the current but loses more voltage than you set as the limit.

The first "Works" row is the smallest wire that does both jobs, which is what the suggested wire shows. Use the table to see the cost of going one size up: often the next size buys a much lower drop for a modest price difference, which is worth it on a load that runs many hours, such as a well pump, a shop compressor or an EV charger.

If you are quoting a feeder plus branch circuits, work out the feeder at its own load and length first, then each branch. Keep the two drops added together under 5%, for example 2% on the feeder and 3% on the farthest branch.

Where the simple formula stops

  • Large conductors. The K method uses DC resistance. For big AC conductors, especially in steel conduit, reactance adds to the drop, and NEC Chapter 9, Table 9 gives the AC values. Above about 1/0 the simple method starts to understate the drop.
  • Temperature. K is for 75°C. A lightly loaded wire runs cooler, with a little less resistance, so the formula is slightly conservative.
  • Motor starting. A motor draws several times its running current for a moment when it starts. Check the starting dip separately for long runs to well pumps and compressors.

When you have the size, build the estimate in Koira with the wire, conduit, breaker and labor as their own lines. For labor rates, see the electrician labor rate calculator.

Last checked October 8, 2026. More for your trade: how electricians run on Koira.

FAQ

How do I calculate voltage drop?

For single phase, VD = 2 × K × amps × one-way length ÷ circular mils, with K = 12.9 for copper and 21.2 for aluminum. Divide by the voltage for percent. 16 A on 100 ft of 12 AWG copper at 120 V drops 6.32 V, 5.27%.

What is the maximum voltage drop allowed by the NEC?

The NEC does not set a general maximum. Informational notes in 210.19 and 215.2 suggest 3% on branch circuits and 5% total for feeder plus branch for reasonable efficiency. Local codes and specifications can make limits mandatory.

What size wire do I need for 100 feet?

It depends on the current and voltage. At 240 V and 30 A, 10 AWG copper reaches about 97 ft at 3%, so 100 ft needs 8 AWG. At 120 V and 20 A, 12 AWG reaches only about 46 ft at 3%.

What is the K value for copper and aluminum?

About 12.9 ohm-circular mils per foot for copper and 21.2 for aluminum, at 75°C.

Is aluminum wire OK for long runs?

Aluminum has about 64% more resistance than copper, so it needs to be about two sizes larger for the same drop and ampacity. It is common for feeders and service conductors; use connectors and terminals rated for aluminum.

Does voltage drop matter for three phase?

Yes, but the multiplier is 1.732 instead of 2, so the drop for the same current, length and wire is about 13% less than single phase.

We know what works. Leave it to Koira.

☼⚙
Standard⚡ Turbo
● Koira did it● You by hand
Today $9,300$8,100 / $1,200
This week $25,050$18,570 / $6,480
This month $69,300$46,150 / $23,150
Money, just now
Reminded Sean Love, $1,850. Polite reminder with the pay link.
Bids, 9:44 am
Nudged Dana on the kitchen bid. Day 3 follow up. She opened it at 9:12.
Convos, 9:41 am
Texted back a missed call. Walk through booked Thu 10:00.
Voltage Drop Calculator: Wire Size, Copper and Aluminum, NEC | Koira