Conduit fill calculator

Pick the conduit, trade size and wire, and enter how many of each size you are pulling. See the percent fill against the NEC limit, the smallest trade size that works, and how many wires of one size the conduit holds on its own.

40%Limit for 3 or more wires
5 racewaysEMT, IMC, RMC, PVC 40 and 80
FreeNo email, no sign-up
wires
Hots and neutrals. Count every wire, spares too.
wires
wires
Grounds count toward fill.
Conduit fill
17.5%
Fits 3/4 in. EMT (limit 40%)
1/2 in.Smallest EMT that fits
0.0931 sq inWire area
16Most 12 AWG alone in this size
Fill is only one check. More than three current-carrying wires in a raceway lowers each wire's ampacity, and a long pull with bends may need a bigger size than fill allows. The NEC as adopted where you work and the inspector govern. Pull wire only on a de-energized, locked-out circuit.

How we got this

  1. 6 × 12 AWG6 × 0.0133 sq in = 0.0798 sq inTHHN / THWN-2, NEC Chapter 9, Table 5.
  2. 1 × 12 AWG ground1 × 0.0133 sq in = 0.0133 sq inTHHN / THWN-2, NEC Chapter 9, Table 5.
  3. Total wire area0.0931 sq in for 7 wires
  4. Allowed fill40% (three or more wires)NEC Chapter 9, Table 1.
  5. 3/4 in. EMT0.533 sq in inside × 40% = 0.213 sq in allowedNEC Chapter 9, Table 4.
  6. Fill0.0931 ÷ 0.533 = 17.5%, within 40% (up to 16 allowed)All one size: Chapter 9, Table 1, Note 7 rounds the most allowed up when the decimal is 0.8 or more.
Trade sizeInside area, sq inAllowed at 40%FillThis run
1/2 in.0.3040.12230.6%Fits
3/4 in.0.5330.21317.5%Fits
1 in.0.8640.34610.8%Fits
1-1/4 in.1.4960.5986.2%Fits
1-1/2 in.2.0360.8144.6%Fits
2 in.3.3561.3422.8%Fits
2-1/2 in.5.8582.3431.6%Fits
3 in.8.8463.5381.1%Fits
3-1/2 in.11.5454.6180.8%Fits
4 in.14.7535.9010.6%Fits

Sources: PDHonline course E276, Conduit Fill Calculations tables (NEC Chapter 9, Tables 1, 4 and 5); ICC, Area of Conductor Types sample pages (Chapter 9 Table 1 Note 7 and conduit fill examples); NFPA 70, National Electrical Code (Chapter 9, Table 8; 240.4(D)). Checked 2026-10-08.

Add this calculator to your websiteFree. Paste the code into any page builder that takes HTML. It fits its own height and works on phones.
<iframe src="https://www.koira.ai/embed/tools/conduit-fill-calculator" title="Conduit fill calculator" width="100%" height="900" style="width:100%;max-width:100%;height:900px;border:0;display:block" loading="lazy" allow="clipboard-write" data-koira-tool="conduit-fill-calculator"></iframe> <p style="margin:6px 0 0;font-size:13px"><a href="https://www.koira.ai/tools/conduit-fill-calculator" rel="noopener">Free calculator by Koira</a></p> <script>(function(){if(window.__koiraTools)return;window.__koiraTools=1;var ok=["https://www.koira.ai","https://koira.ai"];addEventListener("message",function(e){var d=e.data;if(!d||d.type!=="koira:tool-height"||ok.indexOf(e.origin)<0)return;var f=document.querySelectorAll("iframe[data-koira-tool]");for(var i=0;i<f.length;i++)if(f[i].contentWindow===e.source)f[i].style.height=Math.max(200,Math.min(8000,Math.ceil(+d.height||0)))+"px";});})();</script>
Key takeaways
  • Add up the area of every wire, insulation included, from NEC Chapter 9, Table 5. Divide by the conduit's inside area from Table 4.
  • One wire may fill 53% of the conduit, two wires 31%, three or more 40%. A nipple 24 in. or shorter may fill 60%.
  • Grounds and spares count. When every wire is the same size, a count that comes to 0.8 or more of the next wire rounds up.

How conduit fill is worked out

Conduit fill is the share of a conduit's inside area taken up by the wires in it. The NEC limits it so wires can be pulled without stripping their insulation and so they have air around them to shed heat. The rules sit in Chapter 9 of the NEC, in three tables:

  • Table 1 sets the limit: 53% for one wire, 31% for two, 40% for three or more.
  • Table 4 gives the inside area of each conduit type and trade size.
  • Table 5 gives the area of each insulated wire, insulation included.

The method is the same for every job: look up each wire's area, multiply by how many, add them up, and compare with the conduit's area times the limit. If the wires take up no more than the limit allows, the conduit is big enough for fill.

Fill % = total wire area ÷ conduit inside area × 100

Two wires get the lowest limit because two round wires side by side are as wide as two diameters, and they can wedge across a bend. Three or more settle into a bundle that pulls more easily.

Conduit and wire areas

Inside areas from NEC Chapter 9, Table 4, in square inches, with the 40% figure used for three or more wires:

Trade sizeEMTEMT 40%PVC 40PVC 40, 40%PVC 80Rigid (RMC)
1/2 in.0.3040.1220.2850.1140.2170.314
3/4 in.0.5330.2130.5080.2030.4090.549
1 in.0.8640.3460.8320.3330.6880.887
1-1/4 in.1.4960.5981.4530.5811.2371.526
1-1/2 in.2.0360.8141.9860.7941.7112.071
2 in.3.3561.3423.2911.3162.8743.408
3 in.8.8463.5387.2682.9076.4427.499
4 in.14.7535.90112.5545.02211.25812.882

Wire areas from Chapter 9, Table 5, in square inches:

SizeTHHN / THWN-2XHHW-2THW
14 AWG0.00970.01390.0139
12 AWG0.01330.01810.0181
10 AWG0.02110.02430.0243
8 AWG0.03660.04370.0437
6 AWG0.05070.05900.0726
4 AWG0.08240.08140.0973
2 AWG0.11580.11460.1333
1/00.18550.18250.2223
2/00.22230.21900.2624
4/00.32370.31970.3718
250 kcmil0.39700.39040.4596
500 kcmil0.70730.69840.7901

Schedule 80 PVC has a thicker wall, so it holds noticeably less than Schedule 40 or EMT of the same trade size. Sizing Schedule 80 with EMT numbers is a common mistake.

Worked examples

A 3-wire feeder with a neutral and ground. Three 2 AWG THHN, one 4 AWG THHN neutral and one 8 AWG THHN ground in EMT:

3 × 0.1158 + 0.0824 + 0.0366 = 0.4664 sq in. Five wires, so the limit is 40%. 1 in. EMT allows 0.346, too small. 1-1/4 in. EMT allows 0.598, which works, at 31.2% fill.

Twelve 10 AWG THHN in PVC. 12 × 0.0211 = 0.2532 sq in. In a run of Schedule 40, 3/4 in. allows 0.203, too small, so it takes 1 in. (0.333). As a nipple of 24 in. or less, the 60% limit lets 3/4 in. carry it: 0.508 × 60% = 0.305.

Adding to a conduit that is already in. A 1-1/4 in. rigid conduit carries twelve 10 AWG THWN. How many 12 AWG THHN can be added? 1.526 × 40% = 0.610 sq in allowed, less 12 × 0.0211 = 0.253 already used, leaves 0.357. 0.357 ÷ 0.0133 = 26.8, so 26. The wires are not all one size, so the result is not rounded up.

A nipple of 8 AWG XHHW. An 18 in. length of 1 in. EMT at 60%: 0.864 × 60% = 0.519 ÷ 0.0437 = 11.9. All the wires are the same size and the decimal is over 0.8, so 12 are allowed.

How many wires fit in a conduit

When every wire is the same size and type, the question is simply how many fit. The calculator answers it for the size you pick. For THHN in common sizes, worked from the 40% areas above with the 0.8 rounding rule:

THHN1/2 in. EMT3/4 in. EMT1 in. EMT1-1/4 in. EMT3/4 in. PVC 401 in. PVC 40
14 AWG122235612134
12 AWG91626451525
10 AWG5101628915
8 AWG3691659
6 AWG1471246

The rounding rule is Note 7 to Chapter 9, Table 1: when all the wires are the same size and the count comes to a decimal of 0.8 or more, the next whole number is allowed. 1 in. EMT gives 0.346 ÷ 0.0133 = 25.98 wires of 12 AWG THHN, so 26 are allowed. With mixed sizes you round down. The fill tables in the NEC's Informative Annex C follow the same rule, but only work when every wire is the same size and type.

Fitting the wires is not the same as being able to use them all at full ampacity. More than three current-carrying wires in one raceway lowers each wire's allowable current, so a conduit stuffed to its fill limit often needs bigger wire, or two conduits.

Rules that catch people out

  • Grounds count. Every equipment grounding conductor takes space. An insulated ground uses its Table 5 area. A bare ground uses the smaller bare-wire area from Chapter 9, Table 8; this calculator treats grounds as insulated, which is the same or more.
  • Spares count. A wire pulled for later is a wire in the conduit.
  • Insulation type matters. XHHW and THW are bigger than THHN in the small sizes, so the same count can need the next trade size up.
  • Nipples. A length of 24 in. or less between boxes or enclosures may be filled to 60%. It is also exempt from the ampacity adjustment for more than three current-carrying wires.
  • Cables in conduit. A multiconductor cable counts as one wire, using its outside diameter for the area.
  • Bends and pulls. Fill is the minimum. A long run with several bends pulls far easier one size up.
The NEC and the inspector governThis calculator checks fill against NEC Chapter 9. It does not check ampacity, derating, temperature or the bends in the run. The NEC as adopted where you work and the local inspector decide what is allowed. Pull wire only on a de-energized, locked-out circuit, and leave service and feeder work to a licensed electrician.

EMT, PVC and rigid: what changes the fill

The trade size printed on a conduit is a name, not a measurement. Inside areas differ by type, and the difference is big enough to change the answer:

  • EMT has a thin wall, so its inside area is close to the largest for its trade size. 3/4 in. EMT has 0.533 sq in inside.
  • Rigid metal conduit (RMC) has a heavier wall but a slightly larger bore in most sizes: 0.549 sq in at 3/4 in.
  • IMC sits between the two in wall thickness and holds a little more than EMT in the small sizes: 0.586 sq in at 3/4 in.
  • PVC Schedule 40 is a little smaller than EMT: 0.508 sq in at 3/4 in.
  • PVC Schedule 80 has the thickest wall and the least room: 0.409 sq in at 3/4 in., about a fifth less than EMT.

Where a run changes type, say EMT inside the building and Schedule 80 PVC where it comes out of the ground, size each part for its own type. The smallest bore in the run is the one that sets the pull. The calculator's table under the answer lists every trade size of the type you picked, so you can see where the fill crosses the limit.

Using the answer on a job

Conduit size drives the cost of a run more than the wire count suggests. Fittings, straps, connectors and bending time all go up with each trade size, so it pays to know the smallest size that works and then decide whether to go one up for an easier pull or room for a future circuit.

When the run is sized, build the estimate in Koira with the conduit, fittings, wire and labor as separate lines. For the wire size itself, use the voltage drop calculator; for the boxes at each end, the box fill calculator; and for the service the run feeds from, the electrical load calculator.

Last checked October 8, 2026. More for your trade: how electricians run on Koira.

FAQ

How do you calculate conduit fill?

Add up the area of every wire from NEC Chapter 9, Table 5, insulation included. Divide by the conduit's inside area from Table 4. One wire may fill 53%, two 31%, and three or more 40%.

How many 12 gauge wires can go in 3/4 EMT?

16 THHN. 3/4 in. EMT has 0.533 sq in inside, 40% of that is 0.213, and a 12 AWG THHN wire is 0.0133 sq in, so 0.213 ÷ 0.0133 = 16.0.

What is the maximum conduit fill percentage?

40% for three or more wires, 31% for two and 53% for one, from NEC Chapter 9, Table 1. A nipple 24 in. or shorter may be filled to 60%.

Do ground wires count in conduit fill?

Yes. Every equipment grounding conductor counts. An insulated ground uses its Table 5 area, a bare ground the area from Chapter 9, Table 8.

Why is the limit for two wires lower than for three?

Two round wires side by side can wedge across the inside of the conduit at a bend. Three or more bundle together and pull more easily, so they are allowed 40%.

Can I use Annex C tables for mixed wire sizes?

No. The Annex C tables only work when every wire is the same size and insulation type. For mixed sizes, add up the areas as this calculator does.

We know what works. Leave it to Koira.

☼⚙
Standard⚡ Turbo
● Koira did it● You by hand
Today $9,300$8,100 / $1,200
This week $25,050$18,570 / $6,480
This month $69,300$46,150 / $23,150
Money, just now
Reminded Sean Love, $1,850. Polite reminder with the pay link.
Bids, 9:44 am
Nudged Dana on the kitchen bid. Day 3 follow up. She opened it at 9:12.
Convos, 9:41 am
Texted back a missed call. Walk through booked Thu 10:00.
Conduit Fill Calculator: EMT, PVC and Rigid, NEC Chapter 9 | Koira